Digital Controller
N
A
Digital input
Power supply
Output 1
Output 2
N
1
2
3
4
Relay contact output
No supplied
No supplied
Voltage pulse output : 0/12V DC
Triac (SSR) output
Open collector output
DC mA, mV, V (See Output Signal Code Table, Code : 4 to 8)
Relay contact output
Voltage pulse output : 0/12V DC
Triac (SSR) output
Open collector output
DC mA, mV, V (See Output Signal Code Table, Code : 3 to 8)
24V AC/DC
100 to 240V AC
DO 4 points (DO1 to DO4)
PFF input (Within transformer 100 to 120V AC type)
Digital input : 4 points (DI1 to DI4) <Area selection>
CT input : 2 points
PFF input (Within transformer 200 to 240V AC type)
CT input : 1 point + PFF input (Within transformer 100 to 120V AC type)
CT input : 1 point + PFF input (Within transformer 200 to 240V AC type)
Feedback resistance input
No retransmission output
Not supplied
Not supplied
Communication 1 : RS-232C, Communication 2 : Not supplied • With digital input (DI1 to 4) Area selection
Communication 1 : RS-422A, Communication 2 : Not supplied • With digital input (DI1 to 4) Area selection
Communication 1 : RS-485, Communication 2 : Not supplied • With digital input (DI1 to 4) Area selection
Communication 1 : RS-232C, Communication 2 : RS-485 • With digital input (DI1 to 4) Area selection
Communication 1 : RS-485, Communication 2 : RS-485 • With digital input (DI1 to 4) Area selection
Communication 1 : Not supplied, Communication 2 : RS-485 • With digital input (DI1 to 4) Area selection
White case
Black case
F
D
G
A
W
Z
N
Digital output
CT input,
Power feed
forward (PFF)
input,
Feedback
resistance
Communication
Retransmission
output
Case color
Initial setting
Instrument version
(DI1 to 4)
(OUT1)
(OUT2)
M
V
T
D
N
M
V
N
4
T
D
N
T
1
2
3
4
F
N
1
4
5
W
X
Y
D
Specifications
Model
Model and Suffix Code
FB400 (48 x 96mm 1/8 DIN size)
FB900 (96 x 96mm 1/4 DIN size)
DC mA, mV, V (See Output Signal Code Table, Code : 3 to 8)
Y
6 1 - 5V DC 7 0 - 20mA DC3 0 - 1V DC
8 4 - 20mA DC
5 0 - 10V DC4
0 - 5V DC
Output signal code table
Input range code table
No quick start code (Default setting)
Version symbol
Specify quick start code 1 and 2 (See page 11)
Specify quick start code 1
No quick start code
PID control with AT (Reverse action)
No quick start code
PID control with AT (Direct action)
Heat/Cool PID control with AT
Heat/Cool PID control with AT for extruder (Air cooling type)
Heat/Cool PID control with AT for extruder (Water cooling type)
Position proportional PID control without FBR
Control Method
Input and
range
Quick start code 1
See Input range Code Table
Y
No code
Hardware coding only
Quick start
code 1
No code
* When HBA (heater break alarm) is used, select the "CT input" from the model code.
** When inter-controller communication is used, please specify code "W, X or Y (COM2 : RS-485).
Remote setpoint input is not available with inter-controller communication.
• Universal input, no model code required on hardware code.
<Area selection>
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
-200.0 +400.0˚C
-200.0 +800.0˚C
0.0 400.0˚C
0.0 800.0˚C
-200 +1372˚C
0 400˚C
0 800˚C
-250.0 +800.0˚F
-328.0 +400.0˚F
0.0 800.0˚F
-328 +2502˚F
0 800˚F
0 1600˚F
-200.0 +400.0˚C
-200.0 +800.0˚C
0.0 400.0˚C
0.0 800.0˚C
-200 +1200˚C
0 400˚C
0 800˚C
RangeCodeInput
K35
K40
K09
K10
K41
02
K
K04
KC6
KC4
KA4
KC5
KA1
KA2
J27
J32
J08
J09
J15
J02
J04
K
J
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
-200.0 +700.0˚F
-328.0 +1200.0˚F
0.0 800.0˚F
-328 +2192˚F
0 800˚F
0 1600˚F
-200.0 +400.0˚C
-328.0 +752.0˚F
-50 +1768˚C
-58 +3214˚F
-50 +1768˚C
-58 +3214˚F
-200.0 +700.0˚C
-200 +1000˚C
-328.0 +1292.0˚F
-328 +1832˚F
0 1800˚C
0 3272˚F
0 1300˚C
0 2372˚F
RangeCodeInput
JC7
JC6
JB6
JB9
A1
J
JA2
T19
TC2
S06
SA7
R07
RA7
E21
E06
EA9
EB1
B03
BB2
N02
NA7
J
T
S
R
E
B
N
Thermocouple
to
to
to
to
to
to
to
to
0 1390˚C
0 2534˚F
0 2300˚C
0 4200˚F
0.0 600.0˚C
0.0 1112.0˚F
0.0 900.0˚C
0.0 1652.0˚F
RangeCodeInput
A02
AA2
W03
WA2
U04
B2
U
L04
L
A3
to
to
to
to
to
to
to
to
to
to
-100.00 +100.00˚C
-200.0 +850.0˚C
-200.0 +200.0˚C
-199.99 +199.99˚F
-328.0 +1562.0˚F
-100.00 +100.00˚C
-200.0 +640.0˚C
-199.99 +199.99˚F
-328.0 +1184.0˚F
-200.0 +200.0˚F
RangeCodeInput
D34
D35
D21
DC8
DC9
29
P
P30
PC8
PC9
PD1
Pt100
JPt100
W5Re/W26Re
(NBS)
PLII
(DIN)
U
(DIN)
L
(ASTM)
RTD
RangeCodeInput
101
201
301
401
501
01
6
DC Current • Voltage
0 to 10mV
0 to 100mV
0 to 1V
0 to 5V
0 to 10V
1 to 5V
RangeCodeInput
701
801
901
902
903
0 to 20mA
4 to 20mA
-100 to +100mV
-1 to +1V
-10 to 10mV
0.0 to 100.0%
0.0 to 100.0%
* 0 to 1 VDC output can be specified only for analog retransmission output.
*
*
**
Temperature/Process Controller FB900/400
Model and Suffix Code
8 FB_01E