Digital Input
(DI 1 to 4 : Optional, DI 5 to 7 : Standard)
Power feed forward input
Number of Inputs
Up to 7 points (DI 1 to 4, DI 5 to 7)
Input Rating
Non-voltage contact input
Functions
DI1 to DI4 : Memory area selection + Area set
DI5 to DI7 : Run/Stop, Remote/Local, Auto/Manual,
Alarm interlock reset,
Selectable
• Exclusive power feed transformer is required.
General Specifications
Supply Voltage
a) 90 to 264V AC (Including supply voltage variation)
[Rating : 100 to 240V AC] (50/60Hz selectable)
b) 21.6 to 26.4V AC (Including supply voltage variation)
[Rating : 24V AC] (50/60Hz selectable)
c) 21.6 to 26.4V DC (Ripple rate 10% p-p or less) [Rating:24VDC]
Power Consumption
FB400 : Less than 11.9VA for AC type (at 240V AC)
Less than 8.2VA for 24V AC type
Less than 250mA for 24V DC type
FB900 : Less than 13.0VA for AC type (at 240V AC)
Less than 9.3VA for 24V AC type
Less than 300mA for 24V DC type
Power Failure Effect
A power failure of 20m sec or less will not affect the control action.
If power failure of more than 20m sec occurs, controller will restart with
the state of HOT start 1, HOT start 2 or COLD start (selectable)
Self-Diagnostic Function
Adjustment data check, Back-up check, A/D converter check, etc.
Operating Environments : -10 to 50˚C [14 to 122˚F]
5 to 95% RH.
Absolute humidity : MAX. W.C 29.3g/m
3
dry
air at 101.3kPa.
Memory Backup : Backed up by non-volatile memory (FRAM)
• Data retaining period : Approx. 10 years
Number of writing : Approx. 1,000,000,000,000,000 times.
(Depending on storage and operating conditions.)
Net Weight
FB400 : Approx. 230g
FB900 : Approx. 290g
External Dimensions (W x H x D)
FB400 : 48 x 96 x 60mm
FB900 : 96 x 96 x 60mm
Communications (Optional)
Number of communications
: Up to 2 points
Communication method
: COM1: RS-485, RS-232C, RS-422A
COM2: For Inter-controller communication
Communication speed
:
2400, 9600, 19200, 38400 BPS
Protocol
: ANSI X3.28(1976) 2.5 A4
MODBUS
Bit format
Start bit : 1
Data bit : 7 or 8
For MODBUS 8 bit only
Parity bit : Without, Odd or Even
Stop bit : 1 or 2
Maximum connection
: RS-485 : 32 units (Including host)
RS-422A : 16 units (Including host)
RS-232C : 1 unit
Communication to Controller :
Automatic temperature rise, Cascade control,
Temperature ratio setting, Group STOP/RUN
Feedback Resistance (FBR) Input
Temperature/Process Controller FB900/400
Event (Alarm) (Optional)
Number of Event Setting
Up to 4 points (Event 1 to 4)
Alarms
Type : Deviation High, Low, High/Low, Band,
P
rocess High, Low
Set value High, Low
MV value High, Low
Cool side MV value (MV) High, Low
FBR value High, Low
Control Loop Break Alarm (LBA)
Setting range
Deviation : - (Input span) to + (input span)
Differential gap : 0 to input span
Process, Set value : Same as input range
Differential gap : 0 to input span
MV value, FBR valued : -5.0 to +105.0%
Control loop break alarm (LBA)
:
LBA time : 0 to 7200 sec. (OFF by setting zero)
LBA deadband : 0 to input span
Output
Assignable to digital output (DO1 to 4).
Other Functions
a) Hold/Re-hold action (Valid for deviation/band/process alarm only)
• Hold action is activated at Power-up and STOP to RUN.
Re-hold action is activated at Power-up, STOP to RUN,
and the control set value change.
b) Event action is configurable in case of input abnormality.
c) Energized/de-energized action is configurable.
d) Delay timer : 0.0 to 600.0 sec
e) Interlock (latch) function is configurable.
Digital Output
Number of Sub Output
Up to 4 points (DO1 to DO4)
Output Items
Event output, Heater break alarm (HBA), FAIL
Output Type
Relay output :
Form A contact, 250V AC 1A (resistive load)
(Optional)
(Optional)
Heater Break Alarm
Number of CT Input
Up to 2 points
CT Input type
CTL-6-P-N (30A), CTL-12-S56-10L-N(100A)
• Selectable
Accuracy
± 5% of input value or ± 2A
(whichever is larger)
Display range
0.0 to 100.0A
Output
Assignable to output 2 or digital output (DO2 to 4).
(Optional)
(Optional)
Analog Retransmission Output
Number of Outputs
1 point
Output types
Measured value (PV), Deviation (DEV), Set value (SV), Manipulated
output value (MV)
Output Signal
Current output :
4 to 20mA DC, 0 to 20mA DC
(Load resistance : Less than 600)
Continuous voltage output
:
0 to 1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
(Load resistance : More than 1k)
Resistance value
Standard : 100 to 10k (factory default 135)
Sampling time
0.1 sec (with measuring input sampling time of 0.05 sec)
0.2 sec (with measuring input sampling time of 0.1 sec)
0.5 sec (with measuring input sampling time of 0.25 sec)
• Not available with PFF or CT 2 input.
(Optional)
Remote Setpoint Input
Input
DC voltage (Low), Current :
0 to 1V DC, 0 to 100mV DC, 0 to 10mV DC
4 to 20mA DC, 0 to 20mA DC
DC voltage (High) : 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
PV input and remote setpoint input are not isolated for each other.
Universal input
Sampling time
0.1 sec (with measuring input sampling time of 0.05 sec)
0.2 sec (with measuring input sampling time of 0.1 sec)
0.5 sec (with measuring input sampling time of 0.25 sec)
Accuracy
0.1% of span
(Standard)
Waterproof/Dustproof
(Standard)
NEMA4X, IP66
Waterproof/Dustproof protection only effective from the front in panel
mounted installation.
Specifications
7FB_01E